Fire water tanks

In short

4 plain answers about fire water tanks, written for building managers and fire companies, each dated and reviewed by PMP's compliance manager.

Updated

  • How often does a fire water tank need draining and cleaning?

    Every ten years under AS 1851-2012. An underwater inspection can be used instead of draining. For lined tanks, a little water is left in the bottom so the liner doesn't move.

  • How long does a fire tank liner last?

    It varies, which is why AS 1851-2012 asks for an estimate of the remaining life at the first ten-yearly clean, or when the liner warranty ends if that's sooner. That estimate then sets how often the tank is drained and inspected.

  • What protects the building while the fire tank is out of service?

    That depends on the building and must be planned before the tank is drained — how long it will be out, whether the mains can carry some of the load, and what else needs to be in place. We plan it with the site before we start.

  • Why is the water level in our fire tank dropping?

    Usually because the tank is not refilling, or water is getting out. The common causes are a faulty inlet or float valve, a drain or test valve that is not fully closed, a leak in the liner or tank, or a leak in the pipework.