Sprinklers
In short
6 plain answers about sprinklers, written for building managers and fire companies, each dated and reviewed by PMP's compliance manager.
Updated
- How often do sprinkler heads need testing?
Under AS 1851-2012, a sample of at least 14 heads is removed and laboratory-tested at 25 years, then every 10 years after that. Dry pendent heads are sampled at 10 years. If the sample fails, more heads are tested and replaced as needed.
- What's the difference between a wet pipe and a dry pipe sprinkler system?
A wet pipe system is full of water all the time. A dry pipe system holds air under pressure and only fills with water when a head opens — it's used where pipes could freeze. Dry systems have more parts to service.
- Why did the sprinkler alarm go off when there was no fire?
Common causes are a pressure surge in the water supply, someone working on the system, a leaking head or fitting, or a faulty alarm device. Each has a different fix, so the cause should be identified.
- Can a painted sprinkler head be cleaned?
No. Paint can stop a sprinkler head opening in a fire, or make it slow to open, so a painted head is replaced, not cleaned, with a head of the same type.
- Can we move sprinkler heads for a fitout?
Yes, but the change has to be checked against the system's design, done by a fire services contractor, and tested before the system goes back in service. New walls and ceilings can leave areas without cover if heads are simply moved to suit the ceiling grid.
- What does a sprinkler alarm valve do?
The alarm valve sits on the main water supply to a wet pipe sprinkler system. When a sprinkler head opens and water starts to flow, the valve opens and sends water to the alarms, which sound the bell and signal the fire brigade.