Maintenance & compliance

In short

10 plain answers about maintenance & compliance, written for building managers and fire companies, each dated and reviewed by PMP's compliance manager.

Updated

  • What is AS 1851?

    The Australian Standard for routine service of fire protection systems and equipment. It sets what is inspected, tested and maintained, how often, and what records and reports are kept. The current edition is AS 1851-2012.

  • What is a critical defect?

    Under AS 1851-2012, a defect that makes a system inoperative — for example, a sprinkler system with no water supply. It must be reported to the building before the technician leaves site and confirmed in writing within 24 hours.

  • What is a non-conformance?

    Something missing or wrong that doesn't stop the system working but gets in the way of servicing it — a missing block plan, missing spare heads, illegible labels, or missing design records.

  • What is a yearly condition report?

    A report AS 1851-2012 requires once a year for each building. It summarises the year's servicing, lists outstanding defects and non-conformances, and states the condition of each system.

  • Who is responsible for fire system servicing?

    AS 1851 calls them the "responsible entity" — typically the building owner, the occupier, or the owner's agent. In a strata building, usually the strata company.

  • What do WA building owners have to do about fire safety?

    Under regulation 48A of the Building Regulations 2012 (WA), owners of existing Class 2 to 9 buildings must keep the building's safety measures able to perform to the standard the building was approved to. The penalty is up to $5,000. This is general information, not legal advice.

  • What is baseline data?

    The design and commissioning figures for a system — the benchmark every later test is compared against. AS 1851-2012 treats missing baseline data as a non-conformance.

  • What goes in the fire system logbook?

    A record of every routine service activity and its result, for each fire system. AS 1851-2012 requires logbooks for sprinklers, fire pumps, hydrant systems, fire water tanks and special hazard systems; hose reels and hydrant valves use tags or labels with summary records.

  • What happens if a service is missed?

    The yearly condition report must record the missed service. The service should be carried out as soon as possible and the regular schedule restored.

  • How do we change fire service contractor?

    Check the notice period in your current agreement, then give the new contractor the last reports, logbooks and any defect lists. A good handover means nothing is missed between the last visit of one and the first visit of the other.