Fire pumps & flow testing

In short

17 plain answers about fire pumps & flow testing, written for building managers and fire companies, each dated and reviewed by PMP's compliance manager.

Updated

  • What is a churn test, and why isn't it enough?

    A churn test runs the fire pump with no water flowing out of the system. It proves the pump starts and builds pressure. It can't prove the pump will deliver the flow a fire needs, because nothing is flowing. A worn impeller or a partly blocked suction can pass a churn test and fail a flow test.

  • Why does my jockey pump keep starting?

    Because the system keeps losing pressure, or the jockey pump's pressure switch is set wrong. Common leaks are a valve that isn't fully closed, a dripping drain or test valve, or a leaking fitting. Frequent starting wears the jockey pump out and can hide a bigger leak.

  • How does diesel go bad in a fire pump tank?

    Diesel that sits for a long time collects water from condensation, and bacteria and fungus grow where fuel meets water. The result — often called "diesel bug" — is sludge that blocks filters and can stop the engine. Fire pump tanks are prone to it because the fuel is used so slowly.

  • My fire pump runs, but the pressure is low. Why?

    The usual causes are a worn impeller, a blockage on the suction side, a valve that isn't fully open, air in the pump, or the pump turning slower than it should. A flow test and a look at the suction side usually narrow it down.

  • What's the difference between a flow test and a boosted flow test?

    A flow test measures what the building's own system — its water supply and pumps — can deliver. A boosted flow test adds a fire truck pumping into the booster, the way the fire brigade would in a fire, to prove the system can take the boost and deliver it at the hydrants.

  • What does a fire pump controller actually do?

    It starts the pump when system pressure drops, keeps it running, and raises an alarm when something is wrong — a failed start, a power problem, low fuel, a battery or charger fault. It's the part that decides whether the pump runs in a fire.

  • What is a fire brigade booster?

    The connection point outside a building where the fire brigade connects its truck to the hydrant system. It lets the brigade pump extra water, at higher pressure, into the building's hydrants.

  • Why does a boosted flow test need controlled pressure?

    Because the test has to prove water gets through at the design flow without overloading older pipework. Leaks are found first, by the five-yearly pressure test at 1.5 times working pressure; uncontrolled pressure only adds stress to joints and valves.

  • What should a fire pump service report tell me?

    What was tested, the readings taken, how they compare with last time and with the design figures, what was found, what couldn't be checked and why, and what needs fixing with a price. If a report only says "all OK", ask what was checked.

  • Who needs to know when the fire pump is out of service?

    Whoever looks after fire safety for the building, and the building's occupants if the protection they rely on is reduced. We tell the site before we take a pump out of service and when it's back.

  • Why do diesel fire pump batteries fail?

    Age, a faulty charger, heat in the pump room, or loose and corroded connections. A diesel that won't crank is most often a battery or charger fault. AS 1851-2012 requires engine-start batteries to be replaced at least every two years.

  • How long does a diesel fire pump engine last?

    There is no fixed life. A fire pump engine runs mainly for tests, so its life depends on maintenance, fuel quality, cooling and batteries. Engines are usually replaced when they fail flow tests, need repeated repairs, or parts are no longer available.

  • Should we repair or replace a diesel fire pump engine?

    Repair when the fault is in the parts around the engine — batteries, charger, starter, cooling or fuel. Consider replacement when the engine itself is worn: low oil pressure, heavy smoke or oil use, failed flow tests, or no parts. Testing first shows which.

  • Can a fire pump controller be replaced without replacing the pump?

    Yes. When the pump and its driver are in good condition, the controller can be replaced on its own. The new controller must suit the pumpset and AS 2941-2013, and the pump is tested on automatic and manual starts before it returns to service.

  • What is a fire pump's cut-in pressure?

    The cut-in pressure is the system pressure at which the fire pump controller starts the pump automatically. When a sprinkler or hydrant opens, pressure falls, and the pump starts once it reaches that setting.

  • What's the difference between a diesel and an electric fire pump?

    Both do the same job. An electric fire pump runs from the building's power supply, so it depends on that supply staying on in a fire. A diesel fire pump has its own engine, fuel and batteries, so it keeps running without mains power, but it needs more maintenance.

  • What happens during a yearly fire pump flow test?

    Once a year the fire pump is run at its rated flow, and the flow and pressure it produces are measured. The results are compared with the pump's performance curve and the baseline data, to show whether the pump still does what it was designed to do.