Sprinkler systems — serviced, tested and repaired.

A sprinkler system sits full of water, waiting for the one head above a fire to open. For that to work, the valves have to be open, the alarms have to sound, the water supply has to be there, and the heads have to be clear and in good condition. Routine servicing checks all of that.

In short

PMP services, tests and repairs sprinkler systems across WA to AS 1851-2012, and handles breakdowns 24/7 — for building owners and for fire companies who need additional capacity.

In plain words: A sprinkler system is a network of pipes and heat-activated heads that sprays water on a fire automatically.

Area: all of Western Australia · Updated

What we do

Routine servicing and testing · alarm valve and flow switch tests · water supply tests · repairs and leaks · replacing damaged or painted-over heads · breakdowns and after-hours call-outs · changes for fitouts (see Fitouts).

How often

Sprinkler systems are serviced on the schedule in Australian Standard AS 1851-2012, Section 2:

How oftenWhat's done
Every monthValves checked open and secured, pressures recorded, alarm valves operated, alarms and pump starting devices tested.
Every six monthsFlow switches and valve monitors tested, main drain test, strainers checked.
Every yearA water supply test, pressure-reducing and relief valves proved, and a survey of the building for anything that stops the sprinklers doing their job — new walls, storage stacked too high, blocked or painted heads.
Every five yearsValve seats, washers and packings renewed; gauges checked against a master gauge; special valves overhauled.
After 25 yearsA sample of sprinkler heads is removed and tested by a laboratory, then again every 10 years. Dry pendent heads are sampled at 10 years.

Wet pipe systems

The most common kind: the pipes are full of water all the time, so water reaches the fire the moment a head opens.

Dry pipe systems

The pipes hold air under pressure, and fill with water only when a head opens. Used where pipes could freeze. They have extra parts to service — the air compressor, the dry pipe valve and the air pressure alarms.

Testing sprinkler heads

Sprinkler heads age. After 25 years a sample of heads is taken out and sent to a laboratory to check they open at the right temperature and don't leak. If the sample fails, more are tested and heads are replaced. We arrange the sampling, the testing and any replacement.

Fire companies: we take on routine sprinkler service and repairs on your contracts, as PMP or as you.

Building managers: we service the sprinklers and the pumps and tanks that feed them, on one visit.

What you receive

An AS 1851 service record and logbook entry; a yearly condition report. Workmanship guaranteed for 12 months.

Your paperwork, job by job

Photos that help us price it

  1. The valve set and its gauges
  2. The system's data plate or block plan

Send them with the quote form, text or WhatsApp them to 0439 729 553, or email support@pmpwa.net.au. Already have a service report or defect list? Attach that too.

Related questions

Free · Reply within one business day

Get a free second opinion on your last service report, or a second quote.

Upload it and PMP will tell you what's overdue under AS 1851, which defects are still open and what's close to the end of its life. Already have a quote? We'll give you a second one to compare.

Upload Your Report

Questions people ask

Can you move heads for a fitout?

Yes. PMP designs the change in-house, moves or adds the heads, tests the system and puts it back in service. Heads simply moved to suit a new ceiling grid can leave areas without cover, so every change is checked against the system's design.

Can I paint over a sprinkler head?

No. Paint can stop a head opening or slow it down. Painted heads are replaced, not cleaned.

A sprinkler head is leaking. Is it about to go off?

Not necessarily, but it should be inspected the same day. Call us and we will attend.