Hydrants and hose reels — serviced, tested and repaired.
Hydrants are for the fire brigade. Hose reels are for the people in the building. Both have to work the first time someone opens them, and both need water at the right pressure to do it.
In short
PMP services, tests and repairs fire hydrants and hose reels across WA to AS 1851-2012, including yearly water supply proving tests and five-yearly boosted flow tests with its own fire truck.
In plain words: A fire hydrant system gives the fire brigade a reliable water supply at set points around a building.
Area: all of Western Australia · Updated
Hydrant servicing
Hydrant systems are serviced on the schedule in AS 1851-2012, Section 4:
| How often | What's done |
|---|---|
| Every month | Where the system has fire pumps: pump starting tests and cut-in pressures. |
| Every six months | Water supply valves operated; hydrant valves, the booster, hoses, cabinets and block plan checked. |
| Every year | Every hydrant valve opened; a water supply proving test at the hardest-to-reach hydrant; pressure-reducing and relief valves tested; links to other fire systems proved. |
| Every five years | Where there is a booster: a pressure test of the whole system at one and a half times its working pressure, then a boosted flow test through the booster. Washers, seatings and packings renewed; gauges checked. |
Fire brigade boosters
The booster is where the fire brigade connects its truck. We check it's accessible, signed and working, change its washers every five years, and test through it with our own fire truck.
Hose reels
Hose reels are serviced every six months and every year (AS 1851-2012, Section 9). We check they are accessible, signed, undamaged and free to run out, and once a year we open them fully and check the flow.
Fire companies: hydrant and hose reel service and the five-yearly tests on your contracts, with our own truck.
Building managers: hydrants, hose reels, pumps and tanks, on one schedule and one report.
What you receive
An AS 1851 service record; flow test results where a test was done. Workmanship guaranteed for 12 months.
Photos that help us price it
- The booster cabinet
- A hydrant valve and its outlet
- The block plan
Send them with the quote form, text or WhatsApp them to 0439 729 553, or email support@pmpwa.net.au. Already have a service report or defect list? Attach that too.
Related questions
- How often are hose reels serviced?
Every six months and every year under AS 1851-2012. The yearly service includes opening the reel fully and checking the flow.
- What is a hydrostatic test on a fire hydrant system?
A hydrostatic test raises the whole fire hydrant system to 1.5 times its working pressure to prove the pipework, joints and valves hold without leaking. AS 1851-2012 requires it every five years where a fire brigade booster is fitted, before the booster flow test.
- What is a hydrant block plan?
A block plan is a diagram of the building's hydrant system, mounted at the booster or fire control point. It shows firefighters where the hydrants, valves and pipework are, so they can use the system quickly in a fire.
What our clients say
B2M Contracting supplies labour across the Public Transport Authority upgrade works, and we've called on PMP Plumbing & Fire Services for the fire services side many times: boosted flow tests, hydrant flow tests, new hydrant installations and gas suppression commissioning. On a project of this size every contractor has to be organised, and PMP are. Their technicians turn up ready to work, follow the site rules, get the testing done when it's scheduled and hand over clear results and paperwork every time. When we need fire services work done properly and on time, PMP is who we call.
Free · Reply within one business day
Get a free second opinion on your last service report, or a second quote.
Upload it and PMP will tell you what's overdue under AS 1851, which defects are still open and what's close to the end of its life. Already have a quote? We'll give you a second one to compare.
Questions people ask
How often are hydrants tested?
Under AS 1851-2012, hydrants are checked every six months and every year, including a yearly water supply proving test. Where there's a booster, the system is pressure tested at 1.5 times working pressure every five years, then boosted flow tested.
What is a water supply proving test?
A yearly test that proves the water supply can deliver the flow and pressure the system was designed for, measured at the hydrant that's hardest to reach. It's required every year for hydrant systems under AS 1851-2012.
What is a fire brigade booster?
The connection point outside a building where the fire brigade connects its truck to the hydrant system. It lets the brigade pump extra water, at higher pressure, into the building's hydrants.