Flow testing — proving the system delivers.
A pump that starts isn't proof that a fire system works. Flow testing measures whether the system delivers the water it was designed to deliver, at the pressure it was designed for, at the outlets that matter.
In short
Flow tests prove a hydrant, sprinkler or pump system delivers the water it was designed for. PMP does routine flow tests and the five-yearly boosted flow test with its own fire truck.
In plain words: A flow test measures how much water a system delivers, and at what pressure, at a set point.
Area: all of Western Australia · Updated
Pump and hydrant flow tests
We flow water from the pump's test line or from the hydrants, measure the flow and the pressure, and compare the results with the design figures and with previous tests. A falling result over the years is often the first sign of a worn pump, a blocked pipe or a valve that isn't fully open.
How often: every year. Where hydrants have fire pumps, the pumps are run at 130% of their duty flow and the results recorded (AS 1851-2012, Table 3.4.3). The water supply is proved at the hydrants that are hardest to reach (Table 4.4.3).
Boosted flow testing
In a fire, the fire brigade connects its truck to the building's booster and pumps water into the hydrant system to raise the pressure. A boosted flow test does the same thing, with our own fire truck, to prove the system can take that boost and deliver it at the furthest hydrants.
How often: every five years, after the pressure test (AS 1851-2012, Table 4.4.4).
Pressure testing
The pipework is filled and held at a set pressure for a set time to prove it doesn't leak or fail. It finds weak joints and fittings before a real fire does.
How often: every five years, where the system has a booster. The whole system is held at one and a half times its working pressure, and the boosted flow test is done only once it passes (AS 1851-2012, Table 4.4.4).
Before the test
We look at the system's design data and the last test results, find the booster and the hydrants we'll test from, and plan where the water will go. We arrange any isolations with the site before we start and put everything back afterwards.
What you get
A report with the flows and pressures we measured, the design figures they're compared against, what the difference means, and what needs fixing if anything does.
Fire companies: book our truck and crew for boosted flow tests on your contracts, as PMP or as you.
Building managers: we'll tell you which tests are due and do them in one visit where we can.
Diesel engine failing, or has it failed a flow test?
We repair it, or replace the engine to suit your pump and prove it with a full flow test.
White-label for fire companiesFire company? We work under your brand.
White-label service, testing and repairs: your uniform, your site sign-in, your report forms — and we never approach your client.
What you receive
A results sheet with the measured flows and pressures against the design figures. Workmanship guaranteed for 12 months.
Photos that help us price it
- The block plan or hydrant layout
- The booster cabinet
- The last test results
Send them with the quote form, text or WhatsApp them to 0439 729 553, or email support@pmpwa.net.au. Already have a service report or defect list? Attach that too.
Related questions
- What is a churn test, and why isn't it enough?
A churn test runs the fire pump with no water flowing out of the system. It proves the pump starts and builds pressure. It can't prove the pump will deliver the flow a fire needs, because nothing is flowing. A worn impeller or a partly blocked suction can pass a churn test and fail a flow test.
- What is a water supply proving test?
A yearly test that proves the water supply can deliver the flow and pressure the system was designed for, measured at the hydrant that's hardest to reach. It's required every year for hydrant systems under AS 1851-2012.
- What happens during a yearly fire pump flow test?
Once a year the fire pump is run at its rated flow, and the flow and pressure it produces are measured. The results are compared with the pump's performance curve and the baseline data, to show whether the pump still does what it was designed to do.
What our clients say
B2M Contracting supplies labour across the Public Transport Authority upgrade works, and we've called on PMP Plumbing & Fire Services for the fire services side many times: boosted flow tests, hydrant flow tests, new hydrant installations and gas suppression commissioning. On a project of this size every contractor has to be organised, and PMP are. Their technicians turn up ready to work, follow the site rules, get the testing done when it's scheduled and hand over clear results and paperwork every time. When we need fire services work done properly and on time, PMP is who we call.
Questions people ask
What's the difference between a flow test and a boosted flow test?
A flow test measures what the building's own system — its water supply and pumps — can deliver. A boosted flow test adds a fire truck pumping into the booster, the way the fire brigade would in a fire, to prove the system can take the boost.
How often are hydrants flow tested?
Every year, the water supply is proved at the hydrant that's hardest to reach (AS 1851-2012). Systems with a fire brigade booster also get a boosted flow test every five years, after a pressure test at 1.5 times working pressure.
Do you test for fire companies?
Yes. Fire companies book PMP's truck and crew for boosted flow tests on their contracts, as PMP or under their own brand. PMP never approaches their clients.
My fire pump runs every test. Is that enough?
It proves the pump starts and makes pressure. It doesn't prove it can deliver water at the flow the building needs. That's what a flow test is for.
What do I get after a flow test?
A report with the flows and pressures measured, the design figures they're compared against, what the difference means, and what needs fixing if anything does.