Fire water tanks — inspected, cleaned and repaired.
Where the water main can't supply a fire system on its own, a tank holds the water it needs. The tank has to be full, clean, sound and able to feed the pumps. Sludge, a failing liner or a leaking joint can stop that.
In short
PMP inspects, cleans and repairs fire water tanks across WA to AS 1851-2012, including underwater camera inspections, and reports what it finds with photographs.
In plain words: A fire water tank stores the water a building's fire system draws on when the town supply can't provide enough.
Area: all of Western Australia · Updated
How often
Fire water tanks are serviced on the schedule in AS 1851-2012, Section 5:
| How often | What's done |
|---|---|
| Every month | The tank is full, the level gauges read correctly, and the supply to it is working. |
| Every six months | The float valve that refills the tank and the level indicators are proved. |
| Every year | A full inspection: leaks, loose fittings, corrosion, the roof, hatches, ladders and vents, vermin proofing, algae and anything that has entered the tank. Lined tanks get their liner checked above and below the water. |
| Every ten years | The tank is drained, the sludge removed, the inside cleaned and the tank refilled. An underwater inspection can be used instead of draining — we have underwater cameras for it. |
The ten-yearly drain and clean
It is the most significant work in a tank's life, and it takes the fire system's water supply away while it's done. We plan it with you: when the tank is out, what protects the building meanwhile, and how quickly it can be returned to service. For lined tanks we leave a little water in the bottom so the liner doesn't move, and we clean without sharp tools.
At the first ten-yearly clean — or when the liner's warranty ends, if that's sooner — the liner's remaining life is estimated. That estimate then sets how often the tank is drained and inspected from then on.
Tanks we work on
- Concrete tanks — cracking, leaking joints and spalling concrete.
- Steel and panel tanks — corrosion, leaking panel joints, loose bolts and failing liners.
- Poly and fibreglass (GRP) tanks — cracking, UV damage and fittings.
Repairs
Leaks, roofs, hatches, ladders, float valves, level gauges and liners. We tell you what we found, what is needed to fix it, and whether a repair will last or the tank needs more than a repair.
Fire companies: tank inspections and the ten-yearly clean on your contracts.
Building managers: the tank, the pumps it feeds and the sprinklers and hydrants beyond them — one team.
What you receive
An inspection report with photographs, and the logbook entry. Workmanship guaranteed for 12 months.
Photos that help us price it
- The tank from outside
- The access hatch
- The last inspection report
Send them with the quote form, text or WhatsApp them to 0439 729 553, or email support@pmpwa.net.au. Already have a service report or defect list? Attach that too.
Related questions
- How often does a fire water tank need draining and cleaning?
Every ten years under AS 1851-2012. An underwater inspection can be used instead of draining. For lined tanks, a little water is left in the bottom so the liner doesn't move.
- How long does a fire tank liner last?
It varies, which is why AS 1851-2012 asks for an estimate of the remaining life at the first ten-yearly clean, or when the liner warranty ends if that's sooner. That estimate then sets how often the tank is drained and inspected.
- What protects the building while the fire tank is out of service?
That depends on the building and must be planned before the tank is drained — how long it will be out, whether the mains can carry some of the load, and what else needs to be in place. We plan it with the site before we start.
- Why is the water level in our fire tank dropping?
Usually because the tank is not refilling, or water is getting out. The common causes are a faulty inlet or float valve, a drain or test valve that is not fully closed, a leak in the liner or tank, or a leak in the pipework.
Questions people ask
How often is a fire water tank inspected?
Every month, six months and year under AS 1851-2012, plus the ten-yearly drain and clean. The yearly inspection covers leaks, corrosion, the roof, hatches and vents, and lined tanks get the liner checked above and below the water.
What kinds of fire tanks do you work on?
Concrete, steel and panel, and poly and fibreglass (GRP) tanks. Repairs cover leaks, roofs, hatches, ladders, float valves, level gauges and liners.