Fire pump won't start, trips or won't stop? We fix it.
In short
PMP repairs and overhauls fire pumps, diesel engines and controllers — starter motors, circuit boards, seals, valves — with its own technicians and in-house electrician, 24/7 for breakdowns.
In plain words: A fire pump controller is the panel that starts the pump automatically when pressure drops and monitors it while it runs.
Area: all of Western Australia · Updated
Common faults, and what usually causes them
| What you're seeing | Usual causes |
|---|---|
| Diesel won't crank | Flat or failed batteries, a faulty battery charger, a starter motor or wiring fault. |
| Diesel cranks but won't start | Fuel: empty, blocked filters, contaminated fuel, air in the lines. |
| Diesel starts, then shuts down | Overheating from a cooling fault, low oil pressure, or a controller shutdown. |
| Pump runs but pressure is low | A worn impeller, a blockage on the suction side, a partly closed valve, or air in the pump. |
| Pump won't stop | The controller set to manual run, a pressure switch fault, or the system still losing pressure. |
| Jockey pump starting often | A leak somewhere in the system, or a pressure switch set wrong. |
| Electric pump trips | Motor overload, a supply fault, or a fault in the starter. |
| Alarm on the controller | Depends on the alarm. Read it to us, or send us a photo of the screen. |
This list tells you what we'll look at first. It isn't a substitute for a technician on site.
Controllers
The controller governs how the fire pump operates. We fault-find, repair and replace controllers, set and test pressure switches, and make sure the pump starts on its own when it should.
What happens when you call
A technician talks it through with you, then attends with the parts most likely to be needed. If it can be fixed on the spot, we fix it. If not, you know before we leave what's wrong, what it costs and when it will be done.
While the pump is out
If the fire pump can't run, the building's fire protection is reduced until it's fixed. Tell whoever looks after fire safety for the building. We'll tell you straight away if we find the pump can't be returned to service on the day.
Brands we service
Southern Cross · Pentair Aurora · Fairbanks Nijhuis · NM Fire · NAFFCO · Fire Driver engines · National Motors · Fireguard controllers
And most other makes — if it pumps water in a building, we service and repair it. Send a photo of the nameplate if you are not sure.
Diesel engine failing, or has it failed a flow test?
We repair it, or replace the engine to suit your pump and prove it with a full flow test.
Control panel replacementPump control panel old or faulty?
We replace panels on fire, pressure, sewer, grinder and stormwater pumps — wired by our own electrician.
White-label for fire companiesFire company? We work under your brand.
White-label service, testing and repairs: your uniform, your site sign-in, your report forms — and we never approach your client.
What you receive
An itemised job report, and the logbook entry once the pump is back in service. Workmanship guaranteed for 12 months.
Photos that help us price it
- The controller screen showing the fault
- The pump and engine nameplates
Send them with the quote form, text or WhatsApp them to 0439 729 553, or email support@pmpwa.net.au. Already have a service report or defect list? Attach that too.
Related questions
- Why does my jockey pump keep starting?
Because the system keeps losing pressure, or the jockey pump's pressure switch is set wrong. Common leaks are a valve that isn't fully closed, a dripping drain or test valve, or a leaking fitting. Frequent starting wears the jockey pump out and can hide a bigger leak.
- My fire pump runs, but the pressure is low. Why?
The usual causes are a worn impeller, a blockage on the suction side, a valve that isn't fully open, air in the pump, or the pump turning slower than it should. A flow test and a look at the suction side usually narrow it down.
- What does a fire pump controller actually do?
It starts the pump when system pressure drops, keeps it running, and raises an alarm when something is wrong — a failed start, a power problem, low fuel, a battery or charger fault. It's the part that decides whether the pump runs in a fire.
- Who needs to know when the fire pump is out of service?
Whoever looks after fire safety for the building, and the building's occupants if the protection they rely on is reduced. We tell the site before we take a pump out of service and when it's back.
Questions people ask
My fire pump failed its monthly run — what now?
Call (08) 6118 6104, answered 24/7 — in Perth metro a technician is on site within 4 hours. Tell whoever looks after fire safety for the building, because its fire protection is reduced until the pump is fixed.
Can you fix the controller as well as the pump?
Yes. PMP fault-finds, repairs and replaces fire pump controllers, sets and tests the pressure switches, and makes sure the pump starts on its own when it should.
Why won't my diesel fire pump crank?
Usually flat or failed batteries, a faulty battery charger, or a starter motor or wiring fault.