Fire pump won't start, trips or won't stop? We fix it.

In short

PMP repairs and overhauls fire pumps, diesel engines and controllers — starter motors, circuit boards, seals, valves — with its own technicians and in-house electrician, 24/7 for breakdowns.

In plain words: A fire pump controller is the panel that starts the pump automatically when pressure drops and monitors it while it runs.

Area: all of Western Australia · Updated

If the fire pump is out of action now, call us: (08) 6118 6104, 24 hours. If there is a fire, call 000 first.

Common faults, and what usually causes them

What you're seeingUsual causes
Diesel won't crankFlat or failed batteries, a faulty battery charger, a starter motor or wiring fault.
Diesel cranks but won't startFuel: empty, blocked filters, contaminated fuel, air in the lines.
Diesel starts, then shuts downOverheating from a cooling fault, low oil pressure, or a controller shutdown.
Pump runs but pressure is lowA worn impeller, a blockage on the suction side, a partly closed valve, or air in the pump.
Pump won't stopThe controller set to manual run, a pressure switch fault, or the system still losing pressure.
Jockey pump starting oftenA leak somewhere in the system, or a pressure switch set wrong.
Electric pump tripsMotor overload, a supply fault, or a fault in the starter.
Alarm on the controllerDepends on the alarm. Read it to us, or send us a photo of the screen.

This list tells you what we'll look at first. It isn't a substitute for a technician on site.

Controllers

The controller governs how the fire pump operates. We fault-find, repair and replace controllers, set and test pressure switches, and make sure the pump starts on its own when it should.

What happens when you call

A technician talks it through with you, then attends with the parts most likely to be needed. If it can be fixed on the spot, we fix it. If not, you know before we leave what's wrong, what it costs and when it will be done.

While the pump is out

If the fire pump can't run, the building's fire protection is reduced until it's fixed. Tell whoever looks after fire safety for the building. We'll tell you straight away if we find the pump can't be returned to service on the day.

Brands we service

Southern Cross · Pentair Aurora · Fairbanks Nijhuis · NM Fire · NAFFCO · Fire Driver engines · National Motors · Fireguard controllers

And most other makes — if it pumps water in a building, we service and repair it. Send a photo of the nameplate if you are not sure.

What you receive

An itemised job report, and the logbook entry once the pump is back in service. Workmanship guaranteed for 12 months.

Your paperwork, job by job

Photos that help us price it

  1. The controller screen showing the fault
  2. The pump and engine nameplates

Send them with the quote form, text or WhatsApp them to 0439 729 553, or email support@pmpwa.net.au. Already have a service report or defect list? Attach that too.

Related questions

Questions people ask

My fire pump failed its monthly run — what now?

Call (08) 6118 6104, answered 24/7 — in Perth metro a technician is on site within 4 hours. Tell whoever looks after fire safety for the building, because its fire protection is reduced until the pump is fixed.

Can you fix the controller as well as the pump?

Yes. PMP fault-finds, repairs and replaces fire pump controllers, sets and tests the pressure switches, and makes sure the pump starts on its own when it should.

Why won't my diesel fire pump crank?

Usually flat or failed batteries, a faulty battery charger, or a starter motor or wiring fault.