Fire pumps

Diesel fire pump engines — repaired, or replaced when they can't be.

When the diesel engine on a fire pump won't start reliably, overheats, can't reach full speed or fails its yearly flow test, we find out why. If a repair won't last, we take the old engine out, fit a new one matched to your pump, and prove it with a full flow test.

In short

PMP replaces worn-out and failing diesel engines on fire pumps across WA. We match the new engine to the pump's duty, mount and align it, connect fuel, cooling, exhaust, batteries and the controller, then prove it with a full flow test.

In plain words: A diesel fire pumpset is a fire pump driven by its own diesel engine, so it keeps the sprinklers or hydrants supplied even when the building's power is off.

Area: all of Western Australia · Updated

Signs it's time

  • It is slow to start, or doesn't reach full speed quickly on its monthly test run
  • It failed its yearly flow test — the pump can't make its rated flow and pressure
  • It overheats, or loses coolant, oil or fuel
  • Starter, charging or battery faults keep coming back
  • Heavy smoke, high oil use or low oil pressure
  • Parts for the engine are no longer made, or take months to arrive
A new diesel fire pumpset being craned into place by PMP at an aged care site
A new diesel fire pumpset being craned into place by PMP at an aged care site

Repair or replace?

Most diesel faults are fixed with parts. We only recommend a new engine when a repair won't last — and we show you why.

What we findUsuallyWhy
Flat or old batteries, a failing charger, a worn starter motorRepairThese are parts, not the engine. We replace them and test the starts.
A blocked heat exchanger, failed hoses or a cooling leakRepairCooling parts can be replaced without touching the engine itself.
Fuel faults: contaminated fuel, blocked filters, air in the linesRepairWe clean or replace the fuel parts and run the engine under load.
Low oil pressure, heavy smoke, high oil use, knockingOverhaul or replaceThe engine itself is worn. We price both so you can compare.
Flow test failed and the engine can't reach rated speedReplace, in most casesA worn engine can't drive the pump to its duty. We test first to rule out the pump.
Engine parts no longer availableReplaceAn engine you can't get parts for is one breakdown away from a long outage.

How the change-out works

  1. Inspect and test. We run the pumpset, read the controller and the last flow test, and find out whether the problem is the engine, the pump or the controller.
  2. Price the options. A written quote for repair, overhaul or replacement, with what each costs and how long the pump will be out of service.
  3. Match the engine. The new engine is sized to the pump's rated duty and speed. We check the controller can run it properly; if it can't, we quote to replace the controller at the same time.
  4. Plan the shutdown. Dates agreed with you, and with your fire company if you have one, so the time the system is out of service is planned and kept short.
  5. Install. Old engine out. New engine mounted, coupled and aligned to the pump. Fuel, cooling, exhaust, batteries and controller wiring connected by our own technicians and in-house electrician.
  6. Commission and flow test. Automatic and manual starts tested, then a full flow test with the results recorded, and the logbook updated before we hand it back.

Recent work

Fire pumps

Diesel engine replacement on a fire pump

Shopping centre · Perth western suburbs

Scope
The pump's original diesel engine had reached the end of its service life. The pump itself was sound and was kept.
Delivery
New engine installed and the skid modified to suit, with a new heat-exchanger cooling loop and exhaust. An engine management module was fitted so the existing fire pump controller could run a modern electronically governed engine. Commissioned and returned to service.

Fire pumps

Dual diesel fire pumpset replacement

Residential aged care · Perth inner north

Scope
Replacement of a combined sprinkler and hydrant pump installation: duty and standby diesel pumpsets of 55 kW each, rated at 1,080 L/min at 1,150 kPa, with a new jockey pump and pressure vessel.
Delivery
Factory acceptance testing to AS 2941-2013, then a site load and flow test with a calibrated flow meter through to 130% of the duty point, engine noise readings and a hydrant flow test. Handed over with a Certificate of Compliance and a full operation and maintenance manual.

Who we do it for

Building owners and managers

We quote it, plan the shutdown with you, do the work and hand you the test results. If you have a fire company, we keep them informed.

Fire companies

Send us the job. We do the change-out as PMP or under your name, on your paperwork if you prefer, and we never approach your client.

What you receive

A written repair-or-replace quote before any work starts. When the work is done: the commissioning and flow test results, the logbook entry, and an itemised job report. Workmanship guaranteed for 12 months.

Photos that help us price it

  1. The engine nameplate
  2. The pump nameplate
  3. The controller, front and nameplate
  4. The last flow test result or service report page
  5. A wide photo of the pump room showing the way in

Send them with the quote form, text or WhatsApp them to 0439 729 553, or email support@pmpwa.net.au.

Related questions

Questions people ask

How do I know if my diesel fire pump engine needs replacing?

Repeated starting faults, overheating, heavy smoke or oil use, low oil pressure, a failed yearly flow test, or parts that are no longer made. We test it first and tell you whether a repair will last or the engine should be replaced.

Can you replace just the engine and keep the fire pump?

Yes, when the pump itself is in good condition. We match the new engine to the pump's rated duty and speed, couple and align it, and flow test the pumpset before handing it back.

Our fire pump failed its flow test. Is it the engine?

Not always. A failed flow test can be the engine, a worn pump, a valve, the suction side or the controller settings. We test to find the cause before we quote, so you don't replace the wrong thing.

How long is the fire pump out of service while the engine is changed?

It depends on the pump room and the engine. We tell you in the quote, and plan the dates with you and your fire company so the time out of service is known in advance and kept short.

Will the controller still work with a new engine?

We check before we quote. If the existing controller can't run the new engine properly, we quote to replace it in the same shutdown, so the pump is only out of service once.

Do you do engine change-outs for fire companies?

Yes. We do the work as PMP or under your company's name, with your paperwork if you prefer, and we never approach your client.

Do you replace diesel fire pump engines outside Perth?

Yes. We work across all of Western Australia, including regional and remote sites. Call us to plan the visit.